For the overcurrent and residual current protection of final circuits from 6A-32A. A single module, 2 pole (switched neutral) bidirectional RCBO to BS EN 61009-1.
The ADB9/ADC9 range of RCBO’s aids compliance with BS 7671 (latest edition), where additional protection by means of a 30mA RCD is required.
2 pole switched neutral design and bidirectional functionality, is well adapted for micro-generation applications, where a type A RCBO may be required.
32A In rating verified by test, for continuous loading at 32A when used with 10mm cable in Hager surface mounted switch disconnector and high integrity consumer units e.g 7.4kW EV charger circuits (RDF = 1.0)
Insulation resistance testing (IR test) can be carried out at 500V DC on the load side terminals with the device in the off position, without the need to disconnect the Line or Neutral conductors.
| Breaking Capacity | 6kA |
| Current Rating | 6A |
| Curve Type | B Curve |
| EAN | 3250611037460 |
| Manufacturer Part Code | ADB906R |
| Mounting Type | DIN Rail |
| Number of Poles | 1 Pole + Neutral |
| Product Range | ADB Series |
| Rated Voltage | 440V |
| Residual Current Type | Type A |